The Iris Power - PDTech Deltamaxx instrument is an integrated system that measures dissipation factor, capacitance and partial discharges in stator bars, coils and complete stator windings.
Download BrochureLoss Factor / Capacitance Test
The PDTech DELTAMAXX system measures current through a reference capacitor and test object. The current is measured by the voltage drop across shunt resistors. A 16-bit A/D converter processes these voltages. The phase angle difference between the high voltage and this current is determined by a novel algorithm, which allows the calculation of the loss angle and automatic elimination of several potential error sources.
Partial Discharge Measurement
The DELTAMAXX is configured to extract Partial Discharge pulses from the coupling capacitor internally. Partial Discharge measurement does not require external shunts or additional components, that is, coupling impedance, pre-amplifier, signal processing, and digitising all takes place in the measuring unit.
Specifications For TANd/C Measurement
Additional Specifications For Partial Discharge Option
Call us at +1 905.677.4824 or Toll Free at +1 888-873-4747 or fill out our online quote form below.
This Resource Library is designed to provide current, relevant resources that provide technical knowledge and practical solutions for owners and operators of rotating machines. We encourage you to use the search feature and filters to locate specific resources of interest.
Articles, Technical Papers, & Case Studies
IN THE PAST 15 YEARS, INSURANCE INDUSTRY DATA HAVE indicated that stator end-winding vibration has become the most important ...
BROWSE OUR RESOURCE LIBRARYHands-on, practical experience
Reasons to Take The Course Mechanical, electrical and environmental stresses can cause a breakdown in the inter-laminar insulation on Stator Core…